§92.251. Property standards and inspections.
24 C.F.R. § 92.251
(i) On each level of each housing unit;
(ii) In or near each sleeping area in each housing unit;
(iii) In the basement of each housing unit and in each common area of a project. A hardwired smoke alarm is not required in crawl spaces or unfinished attics of housing units;
(iv) Within 21 feet of any door to a sleeping area measured along a path of travel; and
(v) Where a smoke alarm installed outside a sleeping area is separated from an adjacent living area by a door, a smoke alarm must also be installed on the living area side of the door.
(2) Each hardwired smoke alarm must have an alarm system designed for hearing-impaired persons.
(3) The Secretary may establish additional standards through Federal Register publication.
(4) Following the relevant specifications of the International Code Council (ICC) or the National Fire Protection Association Standard (NFPA) 72 satisfies the requirements of this paragraph (a)(3)(vi)(B).
(i) On each level of each housing unit;
(ii) In or near each sleeping area in each housing unit;
(iii) In the basement of each housing unit, and in each common area of a project. A hardwired smoke alarm is not required in crawl spaces or unfinished attics of housing units;
(iv) Within 21 feet of any door to a sleeping area measured along a path of travel; and
(v) Where a smoke alarm installed outside a sleeping area is separated from an adjacent living area by a door, a smoke alarm must also be installed on the living area side of the door.
(2) Each hardwired smoke alarm must have an alarm system designed for hearing-impaired persons.
(3) The Secretary may establish additional standards through Federal Register publication.
(4) Where the use of hardwired smoke detectors places an undue financial burden on the owner or is infeasible, a participating jurisdiction may provide a written exception to allow the owner to install a smoke detector that uses 10-year non rechargeable, nonreplaceable primary batteries. The smoke detector must be sealed, tamper-resistant, contain a means to silence the alarm, and otherwise comply with the requirements of this section.
(5) Following the relevant specification of the International Code Council (ICC) or the National Fire Protection Association Standard (NFPA) 72 satisfies the requirements of this paragraph (b)(1)(xi)(B).
Notes, amendments, and revision history
Amendments
[78 FR 44670, July 24, 2013, as amended at 81 FR 92635, Dec. 20, 2016; 88 FR 30496, May 11, 2023; 90 FR 870, Jan. 6, 2025]
Authority
Authority: 42 U.S.C. 3535(d) and 12701—12839, 12 U.S.C. 1701x.
Source
Source: 61 FR 48750, Sept. 16, 1996, unless otherwise noted.
Amendments
[78 FR 44670, July 24, 2013, as amended at 81 FR 92635, Dec. 20, 2016; 88 FR 30496, May 11, 2023; 90 FR 870, Jan. 6, 2025]