# §192.736. Compressor stations: Gas detection.

- (a) Not later than September 16, 1996, each compressor building in a compressor station must have a fixed gas detection and alarm system, unless the building is—
  - (1) Constructed so that at least 50 percent of its upright side area is permanently open; or
  - (2) **Located in an unattended field compressor station of 1,000 horsepower (746 kW) or less.**
- (b) Except when shutdown of the system is necessary for maintenance under [paragraph (c)](#c) of this section, each gas detection and alarm system required by this section must—
  - (1) Continuously monitor the compressor building for a concentration of gas in air of not more than 25 percent of the lower explosive limit; and
  - (2) If that concentration of gas is detected, warn persons about to enter the building and persons inside the building of the danger.
- (c) Each gas detection and alarm system required by this section must be maintained to function properly. The maintenance must include performance tests.