# §95.16-50. Instructions.

- (a) Simple, complete operating instructions must be conspicuously located at or near any release station and in the extinguishing agent cylinder storage room.
- (b) On a system in which extinguishing agent cylinders are stored outside the protected space, operating instructions must also:
  - (1) Include a schematic diagram of the system; and
  - (2) Describe alternate methods of discharging the extinguishing agent into protected spaces should the manual releases or stop valve controls fail to operate.