# §95.16-45. Pre-discharge alarms and time delay devices.

- (a) Each system protecting a space with greater than 6,000 cubic feet gross volume or a space less than 6,000 cubic feet gross volume without a suitable horizontal escape route must have a pneumatic pre-discharge alarm and time delay.
  - (1) **The time delay period must—**
    - (i) Last at least 20 seconds;
    - (ii) Be approved by the Officer in Charge, Marine Inspection during system installation; and
    - (iii) Provide enough time for one person to walk from the farthest area of the protected space to the primary exit.
  - (2) The time delay device must be pneumatically operated and have an accuracy of −0/+20 percent of the rated time delay period throughout the operating temperature range and range of delay settings.
- (b) **The pre-discharge alarm must—**
  - (1) Sound for the duration of the time delay;
  - (2) Be conspicuously and centrally located in the protected space and marked as required by [46 CFR 97.37-9](/cfr/46/97.37-9.md);
  - (3) Depend on the extinguishing agent, gas from a pilot cylinder, or a nitrogen cylinder specifically provided to power the alarm for its source of power; and
  - (4) **Be audible over running machinery.**