# §95.16-10. Piping, fittings, valves, nozzles.

- (a) Piping, fittings, and valves must be:
  - (1) In accordance with the manufacturer's approved design, installation, operation, and maintenance manual;
  - (2) Securely supported and when necessary protected against damage;
  - (3) Protected inside and out against corrosion; and
  - (4) **Equipped with—**
    - (i) Dead end lines (dirt traps) that extend at least 2 inches beyond the last nozzle of each distribution line and that are closed with a cap or plug; and
    - (ii) Drains and dirt traps, fitted where necessary to prevent dirt or moisture accumulation and located in accessible locations where possible.
- (b) **Piping requirements.** Piping must be:
  - (1) Used exclusively for extinguishing system purposes;
  - (2) Protected by a pressure relief valve in sections where gas pressure can be trapped between closed valves; and
  - (3) **Welded if it passes through living quarters.**
- (c) **Piping prohibitions.** Piping must not:
  - (1) Use rolled groove or cut groove ends; or
  - (2) **Be fitted with drains or other openings if it passes through living quarters.**
- (d) **Valve requirements.** Valves for system operation must be:
  - (1) Outside the protected space, and
  - (2) **Marked, if serving a branch line, to indicate the space the branch line serves.**
- (e) **Valve prohibitions.** Valves may not be located in any space that could be cut off from the operator in the event of fire in the protected space.