# §95.16-1. Application.

- (a) “Clean agent” means a halocarbon or inert gas used as a fire extinguishing agent.
- (b) A clean agent extinguishing system must comply with this part. Systems contracted for prior to July 9, 2012, may, as an alternative, comply with [46 CFR 95.16-90](/cfr/46/95.16-90.md).
- (c) **Each clean agent system must—**
  - (1) Be of a total flooding type to protect against Class B and Class C hazards as defined in [46 CFR 95.50-5](/cfr/46/95.50-5.md);
  - (2) Address and minimize any hazard to personnel created by the effects of extinguishing agent decomposition products and combustion products, especially the effects of decomposition product hydrogen fluoride (HF), if applicable;
  - (3) Be accompanied by an approved manufacturer's design, installation, operation, and maintenance manual;
  - (4) Be used only to protect enclosed spaces;
  - (5) Not employ electric power for system actuation or controls; and
  - (6) Not use any source of power for alarms in protected spaces, other than the extinguishing agent, gas from pilot cylinders, or gas from cylinders specifically provided to power the alarms.