# §95.15-30. Alarms.

- (a) A protected space must be fitted with an approved audible alarm if:
  - (1) The space is normally accessible to persons onboard while the vessel is being navigated; and
  - (2) **Is not a paint locker or similar small space.**
- (b) **The alarm must—**
  - (1) Sound automatically and audibly for at least 20 seconds before carbon dioxide is discharged into the space;
  - (2) Be conspicuously and centrally located and be marked as required by [46 CFR 97.37-9](/cfr/46/97.37-9.md); and
  - (3) Use stored gas power provided by the extinguishing agent, gas from pilot cylinders, or gas from cylinders specifically provided to power the alarms.
- (c) For systems installed on or after July 1, 1957, alarms are mandatory only for systems required to be fitted with a delayed discharge.