# §76.33-10. Location and spacing of accumulators.

- (a) Smoke accumulators must be located overhead in each compartment. Where liable to physical damage, the accumulators and piping must be suitably protected.
- (b) No spot on the overhead of a protected space may be more than 40 feet from an accumulator.
- (c) Accumulators must not be located closer to the opening of a ventilator than three times the diameter or equivalent diameter of the opening.