# §63.15-7. Alarms.

- (a) An audible alarm must automatically sound when a flame safety system shutdown occurs. A visible indicator must indicate that the shutdown was caused by the flame safety system.
- (b) Means must be provided to silence the audible alarm. The visible indicators must require manual reset.
- (c) For steam boilers, operation of the lower low water cutoff must automatically sound an audible alarm. A visual indicator must indicate that the shutdown was caused by low water.
- (d) For a periodically unattended machinery space, the auxiliary boiler trip alarm required by table 1 to [§ 62.35-50](/cfr/46/62.35-50.md) of this subchapter satisfies the requirements for the audible alarms specified in this section.