# §62.25-15. Safety control systems.

- (a) Minimum safety and trip controls required for specific types of automated vital systems are listed in table 1 to [§ 62.35-50](/cfr/46/62.35-50.md).
- (b) Safety trip controls must not operate as a result of failure of the normal electrical power source unless it is determined to be the failsafe state.
- (c) Automatic operation of a safety control must be alarmed in the machinery spaces and at the cognizant remote-control location.
- (d) Local manual safety trip controls must be provided for all main boilers, turbines, and internal combustion engines.
- (e) **Automatic safety trip control systems must—**
  - (1) Be provided where there is an immediate danger that a failure will result in serious damage, complete breakdown, fire, or explosion;
  - (2) Require manual reset prior to renewed operation of the equipment; and
  - (3) Not be provided if safety limit controls provide a safe alternative and trip would result in loss of propulsion.