# §56.50-10. Special gauge requirements.

- (a) Where pressure-reducing valves are employed, a pressure gauge must be provided on the low-pressure side of the reducing station.
- (b) Fuel oil service and transfer, fire, cargo, and boiler feed pumps must be provided with a discharge pressure gage. Additional information pertaining to fire pumps is in [§ 34.10-5](/cfr/46/34.10-5.md) of subchapter D, [§ 76.10-5](/cfr/46/76.10-5.md) of subchapter H, [§ 95.10-5](/cfr/46/95.10-5.md) of subchapter I, and [§ 108.417](/cfr/46/108.417.md) of subchapter IA, all of this chapter.