# §34.20-10. Controls—T/ALL.

- (a) The foam agent, its container, measuring devices, and other items peculiar to this system shall be of an approved type.
- (b) The foam agent container and the main controls for operating the system shall be located in a protected space not likely to be made inaccessible in the event of a fire in any portion of the cargo area.
- (c) Complete, but simple instructions for the operation of the system shall be located in a conspicuous place at or near the controls.
- (d) All valves shall be marked as required by [§ 35.40-17](/cfr/46/35.40-17.md).
- (e) The deck foam system on each tankship that has a keel laying date on or after January 1, 1975, must be capable of being actuated, including introduction of foam to the foam main, within three minutes of notification of a fire.