# §183.390. Shore power.


A vessel with an electrical system operating at more than 50 volts, which is provided with a means to connect to shore power, must meet the following:

- (a) A shore power connection box or receptacle must be permanently installed at a convenient location;
- (b) A cable connecting the shore power connection box or receptacle to the switchboard or main distribution panel must be permanently installed;
- (c) A circuit breaker must be provided at the switchboard or main distribution panel for the shore power connection; and
- (d) The circuit breaker, required by [paragraph (c)](#c) of this section, must be interlocked with the vessel's power sources so that shore power and the vessel's power sources may not be operated simultaneously.