# §183.324. Dual voltage generators.

- (a) A dual voltage generator installed on a vessel shall be of the grounded type, where:
  - (1) The neutral of a dual voltage system must be solidly connected at the switchboard's neutral bus; and
  - (2) The neutral bus shall be connected to ground.
- (b) The neutral of a dual voltage system must be accessible for checking the insulation resistance of the generator to ground before the generator is connected to the bus.
- (c) Ground detection must be provided that:
  - (1) For an alternating current system, meets [§ 111.05-27](/cfr/46/111.05-27.md) in subchapter J of this chapter; and
  - (2) For a direct current system, meets [§ 111.05-29](/cfr/46/111.05-29.md) in subchapter J of this chapter.