# §181.310. Fire main and hydrants.

- (a) A vessel that has a power driven fire pump must have a sufficient number of fire hydrants to reach any part of the vessel using a single length of firehose.
- (b) Piping, valves, and fittings in a fire main system must comply with [subpart G](/cfr/46/subpartG.md), [part 182](/cfr/46/part182.md), of this chapter.
- (c) Each fire hydrant must have a valve installed to allow the firehose to be removed while the fire main is under pressure.
- (d) Spanner wrenches must be provided where a 40 millimeter (1.5 inch) diameter firehose is required by [§ 181.320(b)](/cfr/46/181.320.md?p=b). Existing vessels as of July 22, 2016 have 180 days to comply with this requirement.