# §169.690. Lighting branch circuits.


Each lighting branch circuit must meet the requirements of [§ 111.75-5](/cfr/46/111.75-5.md) of this chapter, except that—

- (a) Appliance loads, electric heater loads, and isolated small motor loads may be connected to a lighting distribution panelboard; and
- (b) Branch circuits in excess of 30 amperes may be supplied from a lighting distribution panelboard.