# §169.667. Switchboards.

- (a) Each switchboard must be in as dry a location as practicable, accessible, protected from inadvertent entry, and adequately ventilated. All uninsulated current carrying parts must be mounted on nonabsorbent, noncombustible, high dielectric insulating material.
- (b) Each switchboard must be—
  - (1) Totally enclosed; and
  - (2) **Of the dead front type.**
- (c) Each ungrounded conductor of a circuit must have at the point of attachment to the power source either—
  - (1) A Circuit breaker; or
  - (2) **A switch and fuse.**
- (d) Each switch other than one mounted on a switchboard must be of the enclosed type.