# §162.161-4. Construction.

- (a) Each pressure vessel must comply with 46 CFR [147.60(a)](/cfr/46/147.60.md?p=a) and [(b)](/cfr/46/147.60.md?p=b).
- (b) Each system must be capable of operation without an external power source.
- (c) Manual actuation for the system must be by mechanical or pneumatic means.
- (d) Automatically actuated systems must be released by pneumatic or fusible element detection systems.
- (e) Each system installed with the extinguishing agent cylinders stored inside a protected space of 6,000 cubic feet or less must use automatic actuation as the primary means of actuation and have a remote backup manual mechanical actuator.
- (f) Each container charged with nitrogen must have a pressure gauge.

## Notes