# §147.66. Inert gas fire extinguishing systems.

- (a) Inert gas cylinders forming part of a clean agent fixed fire extinguishing system must be retested every 12 years.
- (b) An inert gas cylinder must be removed from service if it:
  - (1) Leaks;
  - (2) Is dented, bulging, severely corroded, or otherwise weakened;
  - (3) Has lost more than 5 percent of its tare weight; or
  - (4) **Has been involved in a fire.**
- (c) Flexible connections between cylinders and discharge piping for fixed inert gas fire extinguishing systems must be renewed or retested in accordance with [section 7.3](/cfr/46/7.3.md) of NFPA 2001 (incorporated by reference, see [§ 147.7](/cfr/46/147.7.md)), except that this renewal or retesting must occur when the cylinders are retested.