# §143.260. Fuel shutoff requirements.

- (a) This section does not apply to an excepted towing vessel as defined in [§ 136.110](/cfr/46/136.110.md) of this subchapter.
- (b) To stop the flow of fuel in the event of a fire or break in the fuel line, a remote fuel shutoff valve must be fitted on any fuel line that supplies fuel directly to a propulsion engine or generator prime mover.
- (c) The valve must be installed in the fuel piping directly outside of the fuel oil supply tank.
- (d) The valve must be operable from a safe place outside the space where the valve is installed.
- (e) Each remote valve control must be marked in clearly legible letters, at least 25 millimeters (1 inch) high, indicating the purpose of the valve and the way to operate it.