# §130.450. Machinery alarms.

- (a) Each alarm required by [§ 130.460](/cfr/46/130.460.md) of this subpart must be of the self-monitoring type that will both show visibly and sound audibly upon an opening or break in the sensing circuit.
- (b) The visible alarm must show until it is manually acknowledged and the condition is corrected.
- (c) The audible alarm must sound until it is manually silenced.
- (d) No silenced alarm may prevent any other audible alarm from sounding.
- (e) Each OSV must be provided with means for testing each visible and audible alarm.
- (f) Each OSV must provide battery power for the alarm required by [§ 130.460(a)(8)](/cfr/46/130.460.md?p=a-8) of this subpart.