# §113.25-16. Overcurrent protection.

- (a) Each fuse in a general emergency alarm system must meet the requirements of [part 111](/cfr/46/part111.md), [subpart 111.53](/cfr/46/subpart111.53.md), of this chapter.
- (b) Each overcurrent protection device must cause as wide a differential as possible between the rating of the branch circuit overcurrent protection device and that of the feeder overcurrent protection device.
- (c) The capacity of the feeder overcurrent device must be as near practicable to 200 percent of the load supplied. The capacity of a branch circuit overcurrent device must not be higher than 50 percent of the capacity of the feeder overcurrent device.