# §112.30-5. Transfer of emergency loads.


If there is a reduction of potential of the normal source by 15 to 40 percent, the emergency loads under [§ 112.15-5](/cfr/46/112.15-5.md) must transfer automatically from the normal source to the emergency power source.


## Notes

### Authority

Authority: 46 U.S.C. 3306, 3703; DHS Delegation No. 00170.1, Revision No. 01.2.

### Source

Source: CGD 74-125A, 47 FR 15267, Apr. 8, 1982, unless otherwise noted.