# §111.53-1. General.

- (a) **Each fuse must—**
  - (1) **Meet the general provisions of Article 240 of NFPA 70 or IEC 60092-202—** 2016 (both incorporated by reference; see “[§ 110.10-1](/cfr/46/110.10-1.md) of this subchapter) as appropriate.
  - (2) Have an interrupting rating sufficient to interrupt the asymmetrical RMS short-circuit current at the point of application; and
- (b) Renewable link cartridge-type fuses must not be used.
- (c) Each fuse installation must provide for ready access to test the condition of the fuse.