# §111.51-3. Short-circuit calculations for systems below 1500 kilowatts.


The following short-circuit assumptions must be made for a system with an aggregate generating capacity below 1500 kilowatts, unless detailed computations in accordance with [§ 111.51-4](/cfr/46/111.51-4.md) are submitted:

- (a) The maximum short-circuit current of a direct current system must be assumed to be 10 times the aggregate normal rated generator currents plus 6 times the aggregate normal rated currents of all motors that may be in operation.
- (b) The maximum asymmetrical short-circuit current for an alternating current system must be assumed to be 10 times the aggregate normal rated generator currents plus 4 times the aggregate normal rated currents of all motors that may be in operation.
- (c) The average asymmetrical short circuit current for an alternating-current system must be assumed to be 8 1/2 times the aggregate normal rated generator currents plus 3 1/2 times the aggregate normal rated currents of all motors that may be in operation.