# §111.51-2. Short-circuit calculations.

- (a) The available short-circuit current must be computed—
  - (1) From the aggregate contribution of all generators that can simultaneously operate in parallel;
  - (2) From the largest probable motor load; and
  - (3) **With a three-phase fault on the load terminals of the protective device.**
- (b) The calculated currents must be used to select suitably rated equipment and to allow the selection and setting of protective devices.