# §111.30-5. Construction.

- (a) All low voltage and medium voltage switchboards (as low and medium are determined within the standard used) must meet—
  - (1) For low voltages, either [section 6](/cfr/46/6.md) (except [section 6.3.3](/cfr/46/6.3.3.md)) of IEEE 45.7-2012 or of IEC 60092-302:1997 (both incorporated by reference; see [§ 110.10-1](/cfr/46/110.10-1.md) of this subchapter), as appropriate.
  - (2) For medium voltages, either [section 7](/cfr/46/7.md) of IEEE 45.7-2012 or IEC 60092-503:2007 (incorporated by reference; see [§ 110.10-1](/cfr/46/110.10-1.md) of this subchapter), as appropriate.
- (b) Each switchboard must be fitted with a dripshield unless the switchboard is a deck-to-overhead mounted type which cannot be subjected to leaks or falling objects.