# §111.103-7. Ventilation stop stations.


Each power ventilation system stop station must:

- (a) Be protected by an enclosure with a glass-paneled door on the front;
- (b) Be marked, “In Case of Fire Break Glass and Operate Switch to Stop Ventilation;”
- (c) Have the “stop” position of the switch clearly identified;
- (d) Have a nameplate that identifies the system controlled; and
- (e) **Be arranged so that damage to the switch or cable automatically stops the equipment controlled.**