# §111.103-1. Power ventilation systems except machinery space ventilation systems.


Each power ventilation system that is not a machinery space ventilation system must have:

- (a) **A control to stop the ventilation that is—**
  - (1) Outside the space ventilated; and
  - (2) Grouped with the controls for every power ventilation system to which this section is applicable; and
- (b) **In addition to the control required by paragraph (a), a stop control that is—**
  - (1) As far as practicable from the control required by [paragraph (a)](#a) and grouped with the controls for every power ventilation system to which this section is applicable; or
  - (2) The circuit breakers for ventilation grouped on the main switchboard and marked, “In Case of Fire Trip to Stop Ventilation.”