# §111.05-37. Overcurrent devices.

- (a) A permanently grounded conductor must not have an overcurrent device unless the overcurrent device simultaneously opens each ungrounded conductor of the circuit.
- (b) The neutral conductor of the emergency-main switchboard bus-tie must not have a switch or circuit breaker.