# §108.475. Piping.

- (a) Each pipe, valve, and fitting in a foam extinguishing system must meet the applicable requirements in Subchapter F of this chapter.
- (b) Each pipe, valve, and fitting made of ferrous material must be protected inside and outside from corrosion.
- (c) Each pipe, valve, and fitting must have support and protection from damage.
- (d) Each foam extinguishing system must have enough—
  - (1) Dirt traps to prevent the accumulation of dirt in its pipes; and
  - (2) **Drains to remove liquid from the system.**
- (e) Piping in a foam extinguishing system must be used only for discharging foam.