# §108.473. Foam system components.

- (a) Each foam agent, each tank for a foam agent, each discharge outlet, each control, and each valve for the operation of a foam extinguishing system must be approved by the Commandant.
- (b) Each foam agent tank and each control and valve for the operation of a foam extinguishing system with outlets in a space must be outside the space and must not be in a space that may become inaccessible if a fire occurs in the space.
- (c) Each control for a foam extinguishing system with outlets in a space must be near a main escape from the space.