# §108.405. Fire detection system.

- (a) **Each fire detection system and each smoke detection system on a unit must—**
  - (1) Be approved by the Commandant in accordance with [46 CFR 161.002](/cfr/46/161.002.md); and
  - (2) Have a visual alarm and an audible alarm in the pilothouse or at a normally manned control station for the system.
- (b) Each fire detection system must be divided into zones to limit the area covered by any particular alarm signal.
- (c) **Each visual alarm must—**
  - (1) Have a chart or diagram next to the alarm that shows the location of the zones in the system and that contains the instructions for operating, and testing the system;
  - (2) When activated show the zone in the system where fire has been detected; and
  - (3) **Be in a noticeable location in the pilothouse or control station.**