# §108.185. Ventilation for enclosed classified locations.

- (a) The ventilation system for each enclosed classified location must be designed to maintain a pressure differential between the enclosed classified location and each non-classified location adjacent to the enclosed classified location, so as to prevent the discharge of ignitable gases into the non-classified adjacent locations.
- (b) Each air intake must be outside of enclosed classified locations.
- (c) Each unit must have alarms that are powered independently of the ventilation motor power and control circuitry and sound at a continuously manned station when—
  - (1) Gas is present in an enclosed classified location; or
  - (2) **The ventilation system for the space is not working.**
- (d) Each ventilation system for enclosed classified locations must provide a complete change of air every five minutes.