# §62.14442. What must my inspection include?

- (a) At a minimum, you must do the following during your HMIWI equipment inspection:
  - (1) Inspect all burners, pilot assemblies, and pilot sensing devices for proper operation, and clean pilot flame sensor as necessary;
  - (2) Check for proper adjustment of primary and secondary chamber combustion air, and adjust as necessary;
  - (3) Inspect hinges and door latches, and lubricate as necessary;
  - (4) Inspect dampers, fans, and blowers for proper operation;
  - (5) Inspect HMIWI door and door gaskets for proper sealing;
  - (6) Inspect motors for proper operation;
  - (7) Inspect primary chamber refractory lining, and clean and repair/replace lining as necessary;
  - (8) Inspect incinerator shell for corrosion and/or hot spots;
  - (9) Inspect secondary/tertiary chamber and stack, and clean as necessary;
  - (10) Inspect mechanical loader, including limit switches, for proper operation, if applicable;
  - (11) Visually inspect waste bed (grates), and repair/ seal, as necessary;
  - (12) For the burn cycle that follows the inspection, document that the incinerator is operating properly and make any necessary adjustments;
  - (13) Inspect air pollution control device(s) for proper operation, if applicable;
  - (14) Inspect waste heat boiler systems to ensure proper operation, if applicable;
  - (15) Inspect bypass stack components;
  - (16) Ensure proper calibration of thermocouples, sorbent feed systems and any other monitoring equipment; and
  - (17) Include inspection elements according to manufacturer's recommendations; and
  - (18) **Generally observe that the equipment is maintained in good operating condition.**
- (b) At a minimum, you must do the following during your air pollution control device inspection:
  - (1) Inspect air pollution control device(s) for proper operation, if applicable;
  - (2) Ensure proper calibration of thermocouples, sorbent feed systems and any other monitoring equipment; and
  - (3) Include inspection elements according to manufacturer's recommendations; and
  - (4) **Generally observe that the equipment is maintained in good operating condition.**

## Notes

### Amendments

[65 FR 49881, Aug. 15, 2000, as amended at 78 FR 28068, May 13, 2013]