kind: "section"
citation: "40 C.F.R. § 60.155"
title: "40"
number: "60.155"
heading: "Reporting."
url: "https://uscodex.org/cfr/40/60.155"
---

# §60.155. Reporting.

- (a) The owner or operator of any multiple hearth, fluidized bed, or electric sludge incinerator subject to the provisions of this subpart shall submit to the Administrator semi-annually a report in writing which contains the following:
  - (1) A record of average scrubber pressure drop measurements for each period of 15 minutes duration or more during which the pressure drop of the scrubber was less than, by a percentage specified below, the average scrubber pressure drop measured during the most recent performance test. The percent reduction in scrubber pressure drop for which a report is required shall be determined as follows:
    - (i) For incinerators that achieved an average particulate matter emission rate of 0.38 kg/Mg (0.75 lb/ton) dry sludge input or less during the most recent performance test, a scrubber pressure drop reduction of more than 30 percent from the average scrubber pressure drop recorded during the most recent performance test shall be reported.
    - (ii) For incinerators that achieved an average particulate matter emission rate of greater than 0.38 kg/Mg (0.75 lb/ton) dry sludge input during the most recent performance test, a percent reduction in pressure drop greater than that calculated according to the following equation shall be reported:
  - (2) A record of average oxygen content in the incinerator exhaust gas for each period of 1-hour duration or more that the oxygen content of the incinerator exhaust gas exceeds the average oxygen content measured during the most recent performance test by more than 3 percent.
- (b) The owner or operator of any multiple hearth, fluidized bed, or electric sludge incinerator from which the average particulate matter emission rate measured during the performance test required under [§ 60.154(d)](/cfr/40/60.154.md?p=d) exceeds 0.38 g/kg of dry sludge input (0.75 lb/ton of dry sludge input) shall include in the report for each calendar day that a decrease in scrubber pressure drop or increase in oxygen content of exhaust gas is reported a record of the following:
  - (1) **Scrubber pressure drop averaged over each 1-hour incinerator operating period.**
  - (2) **Oxygen content in the incinerator exhaust averaged over each 1-hour incinerator operating period.**
  - (3) Temperatures of every hearth in multiple hearth incinerators; of the bed and outlet of fluidized bed incinerators; and of the drying, combustion, and cooling zones of electric incinerators averaged over each 1-hour incinerator operating period.
  - (4) **Rate of sludge charged to the incinerator averaged over each 1-hour incinerator operating period.**
  - (5) **Incinerator fuel use averaged over each 8-hour incinerator operating period.**
  - (6) **Moisture and volatile solids content of the daily grab sample of sludge charged to the incinerator.**
- (c) The owner or operator of any sludge incinerator other than a multiple hearth, fluidized bed, or electric incinerator or any sludge incinerator equipped with a control device other than a wet scrubber shall include in the semi-annual report a record of control device operation measurements, as specified in the plan approved under [§ 60.153(e)](/cfr/40/60.153.md?p=e).

## Notes

### Amendments

[53 FR 39417, Oct. 6, 1988]

### Authority

Authority: 42 U.S.C. 7401 et seq.

### Source

Source: 36 FR 24877, Dec. 23, 1971, unless otherwise noted.

### Amendments

[53 FR 39417, Oct. 6, 1988]