kind: "section"
citation: "40 C.F.R. § 280.11"
title: "40"
number: "280.11"
heading: "Installation requirements for partially excluded UST systems."
url: "https://uscodex.org/cfr/40/280.11"
---

# §280.11. Installation requirements for partially excluded UST systems.

- (a) Owners and operators must install an UST system listed in § [280.10(c)(1)](/cfr/40/280.10.md?p=c-1), [(3)](/cfr/40/280.10.md?p=c-3), or [(4)](/cfr/40/280.10.md?p=c-4) storing regulated substances (whether of single or double wall construction) that meets the following requirements:
  - (1) Will prevent releases due to corrosion or structural failure for the operational life of the UST system;
  - (2) Is cathodically protected against corrosion, constructed of non-corrodible material, steel clad with a non-corrodible material, or designed in a manner to prevent the release or threatened release of any stored substance; and
  - (3) **Is constructed or lined with material that is compatible with the stored substance.**
- (b) Notwithstanding [paragraph (a)](#a) of this section, an UST system without corrosion protection may be installed at a site that is determined by a corrosion expert not to be corrosive enough to cause it to have a release due to corrosion during its operating life. Owners and operators must maintain records that demonstrate compliance with the requirements of this paragraph for the remaining life of the tank.

## Notes

### Authority

Authority: 42 U.S.C. 6912, 6991, 6991(a), 6991(b), 6991(c), 6991(d), 6991(e), 6991(f), 6991(g), 6991(h), 6991(i).

### Source

Source: 80 FR 41623, July 15, 2015, unless otherwise noted.