# §149.660. What are the requirements for emergency power?

- (a) Each pumping platform complex must have emergency power equipment including a power source, associated transforming equipment, and a switchboard to provide power to simultaneously operate all of the following for a continuous period of 18 hours:
  - (1) Emergency lighting circuits;
  - (2) Aids to navigation equipment;
  - (3) Communications equipment;
  - (4) Radar equipment;
  - (5) Alarm systems;
  - (6) Electrically operated fire pumps; and
  - (7) Other electrical equipment identified as emergency equipment in the operations manual for the deepwater port.
- (b) **The equipment required by paragraph (a) of this section must—**
  - (1) All be located in the same space; and
  - (2) Contain only machinery and equipment for the supply of emergency power (i.e., no oil or natural gas transfer pumping equipment) in accordance with [46 CFR 112.05](/cfr/46/112.05.md).