kind: "section"
citation: "33 C.F.R. § 149.413"
title: "33"
number: "149.413"
heading: "On a manned deepwater port, what spaces require a fixed fire extinguishing system?"
url: "https://uscodex.org/cfr/33/149.413"
---

# §149.413. On a manned deepwater port, what spaces require a fixed fire extinguishing system?


The manned deepwater port spaces or systems listed in [paragraphs (a) through (c)](#a..c) of this section must be protected by an approved fixed gaseous or other approved fixed-type extinguishing system.

- (a) Paint lockers with a carrying capacity of more than 200 cubic feet, and similar spaces containing flammable liquids.
- (b) **Galley ranges or deep fat fryers.**
- (c) Each enclosed space containing internal combustion or gas turbine machinery with an aggregate power of more than 1,000 B.H.P., and any associated fuel oil units, purifiers, valves, or manifolds.

## Notes

### Authority

Authority: 33 U.S.C. 1504, 1509; DHS Delegation No. 00170.1, Revision No. 01.4.

### Source

Source: USCG-1998-3884, 71 FR 57651, Sept. 29, 2006, unless otherwise noted.