# §149.125. What are the requirements for the malfunction detection system?

- (a) Each oil and natural gas system, between a pumping platform complex and the shore, must have a system that can detect and locate leaks and other malfunctions, particularly in high-risk areas.
- (b) The marine transfer area on an oil deepwater port must be equipped with a monitoring system in accordance with [§ 154.525](/cfr/33/154.525.md) of this chapter.
- (c) A natural gas deepwater port must be equipped with gas detection equipment adequate for the type of transfer system, including storage and regasification, used. The Commandant (CG-5P) will evaluate proposed leak-detection systems for natural gas on an individual basis.