# §127.609. Dry chemical systems.

- (a) Each marine transfer area for LNG must have a dry chemical system that provides at least two dry chemical discharges to the area surrounding the loading arms, one of which must be—
  - (1) From a monitor; and
  - (2) Actuated and, except for pre-aimed monitors, controlled from a location other than the monitor location.
- (b) The dry chemical system must have the capacity to supply simultaneously or sequentially each hose or monitor in the system for 45 seconds.
- (c) Each dry chemical hose station must have at least one length of hose that—
  - (1) Is on a hose rack or reel; and
  - (2) **Has a nozzle with a valve that starts and stops the flow of dry chemical.**