# §127.201. Sensing and alarm systems.

- (a) Fixed sensors must have audio and visual alarms in the control room and audio alarms nearby.
- (b) **Fixed sensors that continuously monitor for LNG vapors must—**
  - (1) Be in each enclosed area where vapor or gas may accumulate; and
  - (2) Meet [Section 16.4](/cfr/33/16.4.md) of NFPA 59A (incorporated by reference, see [§ 127.003](/cfr/33/127.003.md)).
- (c) **Fixed sensors that continuously monitor for flame, heat, or products of combustion must—**
  - (1) Be in each enclosed or covered Class I, Division 1, hazardous location defined in [Section 500.5(B)(1)](/cfr/33/500.5.md?p=B-1) of NFPA 70 (incorporated by reference, see [§ 127.003](/cfr/33/127.003.md)) and each area in which flammable or combustible material is stored; and
  - (2) Meet [Section 16.4](/cfr/33/16.4.md) of NFPA 59A (incorporated by reference, see [§ 127.003](/cfr/33/127.003.md)).