# §127.1507. Water systems for fire protection.

- (a) Each waterfront facility handling LHG must have a supply of water and a means for distributing and applying the water to protect personnel; to cool storage tanks, equipment, piping, and vessels; and to control unignited leaks and spills in the marine transfer area for LHG except when the evaluation required by [§ 127.1501(a)](/cfr/33/127.1501.md?p=a) indicates otherwise. The evaluation must address fire protection for structures, cargo, and vessels. Each water system must include on the pier or wharf at least one 2 1/2-inch supply line, one 2 1/2-inch fire hydrant, and enough 2 1/2-inch hose to connect the hydrant to the vessel.
- (b) Each water system must fully and simultaneously supply, for at least 2 hours, all fixed fire-protection systems, including monitor nozzles, at their designed flow and pressure for the worst single incident foreseeable, plus 63 L/s (1000 gpm) for streams from hand-held hoses.