# §127.103. Piers and wharves.

- (a) If the waterfront facility handling LNG is in a region subject to earthquakes, the piers and wharves must be designed to resist earthquake forces.
- (b) Substructures, except moorings and breasting dolphins, that support or are within 5 meters (16.4 feet) of any pipe or equipment containing LNG, or are within 15 meters (49.2 feet) of a loading flange, must—
  - (1) Be made of concrete or steel; and
  - (2) **Have a fire endurance rating of not less than two hours.**
- (c) LNG or LPG storage tanks must have the minimum volume necessary for—
  - (1) Surge protection;
  - (2) Pump suction supply; or
  - (3) **Other process needs.**