# §56.4531. Flammable or combustible liquid storage buildings or rooms.

- (a) Storage buildings or storage rooms in which flammable or combustible liquids, including grease, are stored and that are within 100 feet of any person's work station shall be ventilated with a sufficient volume of air to prevent the accumulation of flammable vapors.
- (b) In addition, the buildings or rooms shall be—
  - (1) Constructed to meet a fire resistance rating of at least one hour; or
  - (2) Equipped with an automatic fire suppression system; or
  - (3) Equipped with an early warning fire detection device that will alert any person who could be endangered by a fire, provided that no person's work station is in the building.
- (c) Flammable or combustible liquids in use for day-to-day maintenance and operational activities are not considered in storage under this standard.