# §250.857. Glycol dehydration units.

- (a) You must install a pressure relief system or an adequate vent on the glycol regenerator (reboiler) to prevent over pressurization. The discharge of the relief valve must be vented in a nonhazardous manner.
- (b) You must install the FSV on the dry glycol inlet to the glycol contact tower as near as practical to the glycol contact tower.
- (c) You must install the shutdown valve (SDV) on the wet glycol outlet from the glycol contact tower as near as practical to the glycol contact tower.